Megger 550503 Turns Ratio Tester

The Three-Phase Automatic TTR is designed to measure the turns ratio of power, instrument, and distribution transformers in a substation or manufacturing environment. A rugged and robust design makes this TTR well suited for use in a variety of harsh environments. The TTR is also particularly suited for testing in power transformer manufacturing environments where testing of complex, three-phase substation power transformers can be performed quickly while minimizing the possibility of errors.

The Megger 550503 measures a wide turns ratio range (10,000:1) while also providing high accuracy (0.1%). The operator is able to enter the ratio of the transformer and all of its taps which indicates immediately when a tap is outside the acceptable limits. This also allows for a pass/fail limit so problem taps can be easily flagged. For single person testing a remote control switch allows the operator to test transformers with LTCs very quickly. To improve set up times and remove the need for additional test equipment the unit records ratio errors for bushing CTs to an accuracy of ±0.1% nameplate. A Quick Test Mode is also available that provides a fast determination of the turns ratio for single and three-phase transformers.

Phase deviation of the transformer primary versus secondary can be measured to indicate problems such as partial shorted turns and core faults. This measurement is also useful in verifying phase errors in all types of PTs and CTs. The Megger 550503 displays all values for each test including measured and calculated ratio, exciting current, ratio error, and phase angle deviation thus providing comprehensive and conclusive data along with automatically self-calibrating for each test.

Features

  • Measures the widest turns ratio range in the industry (45,000:1) and provides the highest accuracy (0.1%).
  • Enables the operator to enter the ratio of the transformer and all of it’s taps. This allows the operator to know immediately when a tap is outside the acceptable limits so problem taps can be easily flagged.
  • Comes equipped with a remote-control switch for single person testing. This allows the operator to test transformers with LTCs very quickly.
  • Internal TTR memory records up to 200 three-phase test results.
  • Measures the phase deviation (in minutes) of the transformer primary versus secondary. This quickly indicates problems in the transformer such as partial shorted turns and core faults. This measurement is also useful in verifying phase errors in all types of PTs and CTs.
  • This instrument is ideal for use by power transformer manufacturers. Its unique testing procedures and storage capability allows an operator to set up and test difficult three-phase transformers (with multiple tap changers and bushing CTs) in a fraction of the time than it used to take with other TTRs. This test also includes a pass/fail limit of individual ratios.
  • A Quick Test mode provides a fast determination of the turns ratio for single and three-phase transformers, thus saving time.
  • Rugged, lightweight design ideally suited for a harsh field and substation environment.
  • Three user selectable standards: ANSI, IEC, and Australian. Also meets IEC 1010 as well as other safety standards such as CSA and UL.

Product Details

  • Excitation Voltage: 8, 40, or 80 V rms, automatically or manually selected
  • Excitation Current Range: 0 to 500 mA, 3 digit resolution
  • Turns Ratio Range: 8 V ac: 0.8 to 4000, 5 digit resolution, 40 V ac: 0.8 to 15,000, 5 digit resolution, 80 V ac: 0.8 to 20,000, 5 digit resolution
  • Phase Deviation Range: ±90 degrees, 1 decimal point for the minutes display, 2 decimal points for the degree display, or for the centi-radian display
  • Current (rms) accuracy: ±(2% of reading + 1 digit) Phase Deviation Accuracy: ±3 minutes
  • Protective Devices: Type T fuses per IEC 127 designation, HV & LV shorting relays, heavy-duty varistors, transient voltage suppressors, and gas surge voltage protectors.
  • Measuring Time: 8 to 20 seconds depending on mode of operation and type of transformer
  • Measurement Method: ANSI/IEEE C57.12.90

    Downloads

    Committing to 3, 6 or 12 Months?

    Call us for fantastic long term hire rates.

    Contact Us

    NEED TECHNICAL SUPPORT?

    Call us for fantastic long term hire rates.

    Tech Support

    The Powertech Difference

    • Huge inventory of test and measurement equipment
    • Calibration labs for Electrical, Pressure, Torque, Temperature, Flow, Dimensional and PPE
    • Remote support when you need it
    • 24/7 end to end online web shop
    • If we don’t have the equipment you are looking for – we will find it for you!

    Speak to our experts today