Fluke 434 3ph Power Quality Analyser

The Fluke 434-II Energy Analyzer helps you understand your overall energy consumption and quantify how much energy loss is costing your facility. The Fluke 435-II Power Quality and Energy Analyzer includes the same great features of the 434-II while adding advanced power quality functionality for more in depth troubleshooting. If you need the same advanced functionality as the 435-II a higher frequency, the Fluke 437-II is the must-have power quality analyzer for 400 Hz power systems. Lastly, the Fluke 438-II Power Quality and Motor Analyzer includes all the power quality and energy analysis capabilities that the Fluke 435-II has as well as the ability to measure mechanical motor parameters such as motor speed, torque and mechanical power without the need of mechanical sensors.

Features

  • Power Measurements
  • Power Quality Measurements
  • IEC61000-4-30 Compliance
  • Power, Energy & Loss Calculator
  • Monitor & Trending
  • Inrush, Inverter Efficiency

Product Details

Specifications: Fluke 434-II and 435-II Power Quality and Energy Analyzers

Volt

Model Measurement Range Resolution Accuracy

Vrms (AC + DC) 434-II 1 V to 1000 V phase to neutral 0.1 V ±0.1% of nominal voltage1

435-II 1 V to 1000 V phase to neutral 0.01 V ±0.1% of nominal voltage1

Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage

Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ±5%

Vrms½ 434-II 1 V to 1000 V phase to neutral 0.1 V ± 1 % of nominal voltage

434-II and 435-II 0.1 V ±0.2% of nominal voltage

Vfund 434-II 1 V to 1000 V phase to neutral 0.1 V ± 0.5 % of nominal voltage

435-II 0.1 V ± 0.1 % of nominal voltage

Amps (accuracy excluding clamp accuracy)

Amps (AC + DC) i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts

i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts

1mV/A 1x 5 A to 2000 A 1A ±0.5% ±5 counts

1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts

Apk i430-Flex 8400 Apk 1 Arms ±5%

1mV/A 5500 Apk 1 Arms ±5%

A Crest Factor (CF) 1 to 10 0.01 ±5%

Amps½ i430-Flex 1x 5 A to 6000 A 1 A ±1% ±10 counts

i430-Flex 10x 0.5 A to 600 A 0.1 A ±1% ±10 counts

1mV/A 1x 5 A to 2000 A 1 A ±1% ±10 counts

1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±1% ±10 counts

Afund i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts

i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts

1mV/A 1x 5 A to 2000 A 1 A ±0.5% ±5 counts

1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts

Hz

Hz Fluke 434 @ 50 Hz Nominal 42.50 Hz to 57.50 Hz 0.01 Hz ±0.01 Hz

Fluke 434 @ 60 Hz Nominal 51.00 Hz to 69.00 Hz 0.01 Hz ±0.01 Hz

Fluke 435 @ 50 Hz Nominal 42.500 Hz to 57.500 Hz 0.001 Hz ±0.01 Hz

Fluke 435 @ 60 Hz Nominal 51.00 Hz to 69.00 Hz 0.001 Hz ±0.01 Hz

Power

Watts (VA, var) i430-Flex max 6000 MW 0.1 W to 1 MW ±1% ±10 counts

1 mV/A max 2000 MW 0.1 W to 1 MW ±1% ±10 counts

Power Factor (Cos j/DPF) 0 to 1 0.001 ±0.1% @ nominal load conditions

Energy

kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts

Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts Excluding line resistance accuracy

Harmonics

Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7

Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7

Volts % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%

r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%

Absolute 0.0 to 1000 V 0.1 V ±5%1

THD 0.0% to 100% 0.1% ±2.5%

Amps % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%

r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%

Absolute 0.0 to 600 A 0.1 A ±5% ±5 counts

THD 0.0% to 100% 0.1% ±2.5%

Watts % f or r 0.0% to 100% 0.1% ±n x 2%

Absolute Depends on clamp scaling and V nominal — ±5% ±n x 2% ±10 counts

THD 0.0% to 100% 0.1% ±5%

Phase Angle -360° to +0° 1° ±n x 1°

Flicker

Plt, Pst, Pst (1 min) Pinst 0.00 to 20.00 0.01 ±5%

Unbalance

Volts % 0.0% to 20.0% 0.1% ±0.1%

Amps % 0.0% to 20.0% 0.1% ±1%

Mains Signaling

Threshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies — —

Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz

Relative V % 0% to 100% 0.10% ±0.4%

Absolute V3s (3 second avg.) 0.0 V to 1000 V 0.1 V ±5% of nominal voltage

General Specifications

Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2

Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated

Memory 8GB SD card (SDHC compliant, FAT32 formatted), up to 32GB optionally. Screen save and multiple data memories for storing data including recordings (dependent on memory size).

Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture

Environmental

Operating Temperature 0°C ~ +40°C; +40°C ~ +50°C excl. battery

Storage Temperature -20°C ~ +60°C

Humidity +10°C ~ +30°C: 95% RH non-condensing

+30°C ~ +40°C: 75% RH non-condensing

+40°C ~ +50°C: 45% RH non-condensing

Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V

Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V

Maximum storage altitude 12 km (40,000 ft)

Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity

Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery

Warranty Three years (parts and labor) on main instrument, one year on accessories

View full family specifications »

  1. ±5% if ? 1% of nominal voltage ±0.05% of nominal voltage if < 1% of nominal voltage
  2. 50Hz/60Hz nominal frequency according to IEC 61000-4-30
  3. 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode
  4. For nominal voltage 50 V to 500 V

    Downloads

    Committing to 3, 6 or 12 Months?

    Call us for fantastic long term hire rates.

    Contact Us

    NEED TECHNICAL SUPPORT?

    Call us for fantastic long term hire rates.

    Tech Support

    The Powertech Difference

    • Huge inventory of test and measurement equipment
    • Calibration labs for Electrical, Pressure, Torque, Temperature, Flow, Dimensional and PPE
    • Remote support when you need it
    • 24/7 end to end online web shop
    • If we don’t have the equipment you are looking for – we will find it for you!

    Speak to our experts today