Fluke 1663 Multifunction Tester

The 1663 installation tester delivers the full-featured functionality and advanced measurement capabilities that professional installers need. It is compact and lightweight (less than 1.3 kg) and comes with a padded carrying and waist strap for convenient handling. Operation is intuitive and easily mastered by all levels of workers so you can put it to work immediately for quick and efficient testing to all local regulations. Additional helpful features like On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

Other useful capabilities:

  • Checks wiring polarity to detect broken N wires
  • Measures insulation resistance and loop and line resistance
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Measures motor windings with continuity test
  • Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)
  • Measures RCD switching time and tripping level (ramp test)
  • Measures trip time and current for RCD type A & AC in one test
  • Measures RCD variable current
  • Provides automatic RCD test sequence
  • Includes a phase sequence indicator
  • Safety rated CAT III 500V, CAT IV 300V
  • Comes with hard carrying case, padded carrying and waist strap, and remote control probe and lead

Features

  • Full featured tester for installation professionals
  • Tests to all local regulations and provides test results for complete documentation
  • Tests continuity at L-N, N-PE inputs
  • Tests smooth dc sensitive RCDs (Type B)
  • Tests earth resistance, voltage, and frequency
  • Offers multiple test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V

Product Details

  • AC voltage measurement
  • Range 500 V
  • Resolution 0.1 V
  • Accuracy 45 Hz – 66 Hz 0.8% + 3
  • Input impedance 360 k?
  • Overload protection 660 V rms
  • Continuity testing (RLO)
  • Range (autoranging) 20 ? / 200 ? / 2000 ?
  • Resolution 0.01 ? / 0.1 ? / 1 ?
  • Open Circuit Voltage >4 V
  • Insulation resistance measurement (RISO)
  • Test voltages 50-100-250-500-1000 V
  • Accuracy of tTest voltage (at rated test current) +10%, -0%
  • Test voltage 50 V
  • 100 V
  • 250 V
  • 500 V
  • 1000 V
  • Insulation resistance range 20 M? /50 M?
  • 20 M? / 100 M?
  • 20 M? / 200 M?
  • 20 M? / 200 M? / 500 M?
  • 20 M? / 200 M? / 1000 M?
  • Resolution 0.01 M? / 0.1 M?
    • M? / 0.1 M?
    • M? / 0.1 M?
    • M? / 0.1 M? / 1 M?
    • M? / 0.1 M? / 1 M?
  • Test current 1 mA @ 50 k?
  • mA @ 100 k?
  • mA @ 250 k?
  • mA @ 500 k?
  • mA @ 1 M?
  • Loop and line impedance (ZI)
  • Range 10 ? / 0.001 ? / High current m? mode
  • Resolution 0.01 ? / 0.1 ? / 1 ?
  • Prospective earth fault current, PSC test
  • Range 1000 A / 10 kA (50 kA)
  • Resolution 1 A / 0.1 kA
  • Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
  • RCD testing, RCD types tested
  • RCD Type AC¹
  • G²,S³
  • Model 1663 A4, AC¹, G²,S³
  • Notes ¹Responds to AC
  • ²General, no delay
  • ³Time delay
  • 4Responds to pulsed signal
  • 5Responds to smooth DC signal
  • Tripping speed test (?T)
  • Current settings¹ 10-30-100-300-500-1000 mA – VAR
  • 10-30-100 mA
  • Multiplier x ½, x 1
  • x 5
  • Measurement range RCD Type G 310 ms
  • 50 ms
  • RCD Type S 510 ms
  • 160 ms
  • Notes ¹1000 mA type AC only
  • 700 mA maximum type A in VAR mode
  • VAR mode not available for type B.
  • RCD/FI-Tripping Current Measurement/Ramp Test (I?N)
  • Current range 30% to 110% of RCD rated current¹
  • Step size 10% of I?N²
  • Dwell time Type G 300 ms/step
  • Type S 500 ms/step
  • Measurement accuracy ±5%
  • Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
  • 35% to 140% for Type A (>10 mA)
  • 35% to 200% for Type A (?10 mA)
  • 50% to 200% for Type B
  • ²5% for Type B
  • Notes ¹30% to 150% for Type A I?N > 10 mA
  • 30% to 210% for Type A I?N = 10 mA
  • 20% to 210% for Type B
  • Earth Resistance Test (RE)
  • Range 200 ? / 2000 ?
  • Resolution 0.1 ? / 1?
  • Frequency 128 Hz
  • Output Voltage 25 V
  • Phase Sequence Indication
  • Icon icon phase sequence indicator Phase Sequence indicator is active.
  • General Specifications
  • Size (L x W x H) 10 x 25 x 12.5 cm
  • Weight (incl. batteries) 1.3 Kg
  • Battery size, quantity Type AA, 6 ea.
  • Sealing IP-40
  • Safety Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
  • Overvoltage CAT III / 500V; CAT IV 300V
  • Performance EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition

    Downloads

    Committing to 3, 6 or 12 Months?

    Call us for fantastic long term hire rates.

    Contact Us

    NEED TECHNICAL SUPPORT?

    Call us for fantastic long term hire rates.

    Tech Support

    The Powertech Difference

    • Huge inventory of test and measurement equipment
    • Calibration labs for Electrical, Pressure, Torque, Temperature, Flow, Dimensional and PPE
    • Remote support when you need it
    • 24/7 end to end online web shop
    • If we don’t have the equipment you are looking for – we will find it for you!

    Speak to our experts today