Fluke 1654B Multifunction Tester

The 1654B Installation Tester builds upon the rugged reputation of the earlier 1650 Series, only it's re-designed to meet your need for more productive test tools.

This installation tester offers the following new capabilities:

  • Fast high current loop test
  • Variable RCD current mode for customized settings
  • PASS/FAIL indication for RCD tests
  • Select voltage measurement between L-N, L-PE and N-PE
  • Zero adapter for easy test lead compensation, available as new accessory and also included with standard scope of supply
  • Loop & Line Resistance - m? resolution
  • Test smooth dc sensitive RCDs (Type B)
  • Extended Memory

Features

Safer, easier installation testing.

The 1654B Installation Tester verifies the safety of electrical installations in domestic, commercial and industrial applications. It can ensure that fixed wiring is safe and correctly installed to meet the requirements of IEC 60364, HD 384 and all relevant local standards

Faster

  • Two measurements at once and a dual display. PEFC/PSC and loop impedance are measured and displayed in parallel, saves you more than 50% of test time compared to other loop testers.
  • Additional new high current loop mode. Faster measurements compared to loop tests with non-trip mode for RCD’s.
  • Unique zero adapter for fast, always reliable and accurate test lead and mains cord compensation.
  • Fast voltage measurement between L-N, L-PE and N-PE using the mains cord. No need to change measurement connections.

Safer

  • Earth Volt Touchpad detects raised earth voltages 50 V, indicating potential dangerous situations.
  • Supplied with the SureGrip™ test leads and clips which gives the user a comfortable, reliable grip

Easy

  • Rotary dial knob indicates clearly which function is selected, all functionalities on one spot and no complex multi level menus.
  • Large display with backlight, clear symbols with exceptionally wide viewing angle for easy and safe readings.
  • PASS/FAIL indication for RCD test results.
  • Variable RCD current mode for customized settings.
  • Loop & Line Resistance – m? resolution
  • Test smooth dc sensitive RCDs (Type B)
  • Extended Memory
  • Extended documentation mode (UK only)
  • Rugged & lightweight Withstands a drop of 1 meter.
  • Compact, lightweight (less than 1.3 kg) and padded neck-strap to free your hands for all day testing.

Complete kit

All 1650 models are equipped with detachable leads that can be replaced in case of damage or loss. A durable hard case will protect your instrument in tough field conditions.

Slim probe design with test button

Keeps your eyes on the panel while probing hard to reach points. This remote probe is powered by the tester so always operable (does not require additional batteries).

Zero Adapter

For easy, always reliable and accurate compensation of test leads and mains cords. This adapter can be used for all different kind of mains plugs as well as test accessories like probes, alligator clips etc.

 

Product Details

• Specifications
• AC Voltage Measurement
• Range: 500 V
• Resolution: 0.1 V
• Accuracy (50 – 60 Hz) ± (0.8% + 3 digits)
• Input Impedance 3.3 M?
• Overload Protection 660 Vrms
• Continuity Testing
• Range (autoranging): 20 ?, 200 ?, 2000 ?
• Resolution: 0.01 ?, 0.1 ?, 1 ?
• Test Current: > 200 mA
• Open Circuit Voltage: > 4 V
• Accuracy: ± (1.5%+3 digits)
• Insulation Resistance Measurement
• Test Voltage: 50 – 100 – 250 – 500 – 1000 V
• Test Voltage: 50 V
• Test Current: 1 mA @ 50 k?
• Insulation Range: 10 k? – 50 ??
• Resolution: 0.01 ??
• Accuracy: ± (3% + 3 digits)
• Test Voltage: 100 V
• Test Current: 1 mA @ 100 k?
• Range/Resolution: 20 M?/0.01 M?
• Range/Resolution: 100 M?/0.1 M?
• Accuracy: ± (3% + 3 digits)
• Test Voltage: 250 V
• Test Current: 1 mA @ 250 k?
• Range/Resolution: 20 M?/0.01 M?
• Range/Resolution: 200 M?/0.1 M?
• Accuracy: ± (1.5% + 3 digits)
• Test Voltage: 500 V
• Test Current: 1 mA @ 500 k?
• Range/Resolution: 20 M?/0.01 M?
• Range/Resolution: 200 M?/0.1 M?
• Accuracy: ± (1.5% + 3 digits)
• Range/Resolution: 500 M?/1 M?
• Accuracy: 10%
• Test Voltage: 1000 V
• Test Current: 1 mA @ 1 M?
• Range/Resolution: 20 M?/0.01 M?
• Range/Resolution: 200 M?/0.1 M?
• Accuracy: ± (1.5% + 3 digits)
• Range/Resolution: 500 M?/1 M?
• Accuracy: 10%
• Auto Discharge: Discharge time constant, 0.5 second for
• C = 1 µF or less
• Live Circuit Detection: Inhibits test if terminal voltage > 30 V prior to initiation of test
• Maximum Capacitive Load: Operable with the 5 µF load
• Loop Impedance Measurement (High Current Mode and Non-Trip Mode)
• Range: 100 – 500 VAC (50/60 Hz)
• Input connection: Soft Key selection
• Loop impedance: Phase to earth
• Line impedance: Phase to neutral
• Limit on consecutive tests: Automatic thermal shutdown after 50 consecutive tests at 10 second intervals (typical)
• Max. Test Current. High Current and Non-Trip Modes:
• Maximum Test Current @ 400 V 20 A sinusoidal for 10 ms
• Maximum Test Current @ 230 V 12 A sinusoidal for 10 ms
• Range/Resolution: 20 ?/0.01 ?
• Range/Resolution: 200 ?/0.1 ?
• Range/Resolution: 2000 ?/1 ?
• Accuracy (no Trip mode): ± (3% + 6 digits)
• Accuracy (Hi Current mode): ± (2% + 4 digits)
• PFC, PSC Test
• Computation: PFC or PSC determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance
• Range: 0 – 25 kA
• Resolution (Ik < 1000 A): 1 A Resolution (Ik >= 1000 A): 0.1 kA
• Accuracy: Determined by accuracy of loop resistance and mains voltage measurements.
• RCD Testing ¹
• G General, no delay
• S Time delay
• A Responds to pulsed signal
• AC Responds to AC
• B Responds to AC up to 1000 Hz: responds to AC superposed by DC
• Tripping Time Test (?T)
• Trip Time Accuracy ±(1% Reading + 1 digit)
• Multiplier: x ½
• Current Settings: 10, 30, 100, 300, 500, 1000 mA
• Current Accuracy: +0% – 10%
• RCD Type ¹: G
• Measurement Range: 310 ms (Europe), 2000 ms (UK)
• RCD Type ¹: S
• Measurement Range: 510 ms (Europe), 2000 ms (UK)
• Multiplier x 1
• Current Settings: 10, 30, 100, 300, 500, 1000 mA
• Current Accuracy: +10% – 0%
• RCD Type ¹: G
• Measurement Range: 310 ms
• RCD Type ¹: S
• Measurement Range: 510 ms
• Multiplier: x 5
• Current Settings: 10, 30 mA
• Current Accuracy: ±10%
• RCD Type ¹: G
• Measurement Range: 50 ms
• RCD Type ¹: S
• Measurement Range: 160 ms
• Tripping Current (ramp)
• Current Range: 50% – 110% of RCD’s rated current
• Step Size: 10% of I?N
• Dwell time (Type G): ¹ 300 ms / step
• Dwell time (Type S): ¹ 500 ms / step
• Trip Current Measurement Accuracy: ±5%
• Earth Resistance Test (RE) – Fluke 1653B + 1654B
• Range/Resolution: 200 ?/0.1 ?
• Accuracy: ±(2% + 5 digits)
• Range/Resolution: 2000 ?/1 ?
• Accuracy: ±(3.5% + 10 digits)
• Frequency: 128 Hz
• Compliance Voltage: +25 V
• Phase Sequence Indication
• Icon: Icon Phase Sequence indicator is active
• Display of Phase Sequence:
• Displays 1-2-3 in digital display field for correct sequence.
• Displays 3-2-1 for incorrect phase.
• Dashes in place of a number indicate a valid determination could not be made.
• Environmental Specifications
• Operating Temperature
• -10 °C to 40 °C
• Humidity (Without Condensation)
• 10 to 30 °C: 95%
• 30 to 40 °C: 75%
• Safety Specifications
• Safety Rating
• EN 61010-I CAT III 500V, CAT IV 300V
• Mechanical & General Specifications
• Size
• (L x W x H): 10 x 25 x 12.5 cm
• Weight
• 1.3 kg
• Batteries
• Type AA: 6
• Warranty
• 3 years
• Battery type
• Alkaline supplied, usable with 1.2V NiCD or NiMH rechargeable batteries

    Downloads

    Committing to 3, 6 or 12 Months?

    Call us for fantastic long term hire rates.

    Contact Us

    NEED TECHNICAL SUPPORT?

    Call us for fantastic long term hire rates.

    Tech Support

    The Powertech Difference

    • Huge inventory of test and measurement equipment
    • Calibration labs for Electrical, Pressure, Torque, Temperature, Flow, Dimensional and PPE
    • Remote support when you need it
    • 24/7 end to end online web shop
    • If we don’t have the equipment you are looking for – we will find it for you!

    Speak to our experts today