Omicron CTA CT Analyser

The CT Analyzer automatically determines all relevant current transformer values and compares the results with the selected standard. The device evaluates the current transformer as per the IEC or IEEE standard within seconds with the push of a button.

It facilitates fast and economical on-site testing and calibration of metering and protection current transformers. Manufacturers of current transformers, high voltage transformers and switchgear also use the CT Analyzer for tests during development and production.

Features

  • Range of measurements
  • Ratio and phase accuracy
  • Winding resistance
  • Excitation characteristics (knee points)
  • Composite error (ALF, ALFi, FS, FSi, Vb)
  • Burden impedance
  • Transient CT classes and parameters (TPS, TPX, TPY and TPZ type CTs)
  • Transient dimensioning factor (Ktd)
  • If missing/unknown: CT type, class, ratio, knee point, power factor, nominal burden, operating burden, primary and secondary winding resistance
  • Remanence and residual magnetism
  • Immediate good/bad evaluation

Additional features:

  • Simulate different burdens and currents
  • Analyze the effect of CT saturation
  • Measure VT ratio
  • Multimeter
  • Highest measurement accuracy: 0.02 % / 1 min when calibrating on site
  • Very small and lightweight (< 8 kg / 17.4 lbs), easy to transport for on-site testing
  • Automatic evaluation according to IEC, IEEE and to customized or local/national standards
  • Short commissioning times (duration of the automatic test < 1min)
  • Excellent workplace safety – Tests run at max. 120 V
  • Integration into testing routines using Remote Interface Control

Product Details

How CT Analyzer works

  • Injects low test signals into secondary side of the CT
  • Determines the CT’s equivalent circuit parameters
  • Identifies all relevant CT performance parameters
  • Displays all relevant parameters of the CT and its accuracy at different currents and burdens
  • Evaluates the CT according to the selected standard
  • Determines unknown CT nameplate parameters
  • Demagnetizes the CT after the test.

    Downloads

    Committing to 3, 6 or 12 Months?

    Call us for fantastic long term hire rates.

    Contact Us

    NEED TECHNICAL SUPPORT?

    Call us for fantastic long term hire rates.

    Tech Support

    The Powertech Difference

    • Huge inventory of test and measurement equipment
    • Calibration labs for Electrical, Pressure, Torque, Temperature, Flow, Dimensional and PPE
    • Remote support when you need it
    • 24/7 end to end online web shop
    • If we don’t have the equipment you are looking for – we will find it for you!

    Speak to our experts today