Megger TORKEL 860 Battery Load Unit

When measuring battery capacity by conducting a discharge test, the TORKEL 860 provides excellent discharging capacity plus a broad voltage range and outstanding portability.

The TORKEL 860 is designed primarily for people who travel from place to place to maintain battery systems having different voltages. It features excellent discharging capacity plus a broad voltage range and outstanding portability. This makes it an excellent option when conducting discharge tests on the capacity of standby power batteries in power plants and transformer substations.

Batteries can be tested in service

  • Unit adjusts to include load currents in the test parameters
  • User adjustable alarm and shutdown points to avoid excessive discharge
  • Easily expandable for larger battery banks using TXL extra load units (option)
  • Computerized test operation using TorkelWin software (option)

The TORKEL 860 is used for systems ranging from 12 to 480 V, and discharging can proceed at up to 110 A.

Product Details

  • General
  • Mains voltage: 100 240 V AC, 50 / 60 Hz
  • Power consumption (max): 150 W
  • Protection: Thermal cut-outs, automatic overload
  • Protection
  • Current measurement
  • Display range: 0.0 2999 A
  • Basic inaccuracy: ±(0.5% of reading +0.2 A)
  • Resolution: 0.1 A
  • Internal current measurement
  • Range: 0 300 A
  • Input for clamp-on ammeter
  • Range: 0 1 V
  • mV/A-ratio Software: settable, 0.3 to 19.9 mV/A
  • Input impedance: >1 M?
  • Voltage measurement
  • Display range: 0.0 60 V
  • Basic inaccuracy: ±(0.5% of reading +0.1 V)
  • Resolution: 0.1 V
  • Display range: 0.0 500 V
  • Basic inaccuracy: ±(0.5% of reading +1 V)
  • Resolution: 0.1 V
  • Time measurement
  • Basic inaccuracy: ±0.1% of reading ±1 digit.
  • Load
  • Max battery voltage: 480 V DC
  • Max current: 110 A
  • Max power: 15 kW
  • Load patterns: Constant current, constant power, constant resistance, current or power profile
  • Current setting: 0-110.0 A (2999.9 A) 1)
  • Power setting: 0-15.00 kW (299.99 kW) 1)
  • Resistance setting: 0.1-2999.8 ?
  • Battery voltage range: 5 ranges, selected automatically at start of test
  • Stabilization: ±(0.5% of reading +0.5 A)
  • (For internal current measurement)

    Downloads

    Committing to 3, 6 or 12 Months?

    Call us for fantastic long term hire rates.

    Contact Us

    NEED TECHNICAL SUPPORT?

    Call us for fantastic long term hire rates.

    Tech Support

    The Powertech Difference

    • Huge inventory of test and measurement equipment
    • Calibration labs for Electrical, Pressure, Torque, Temperature, Flow, Dimensional and PPE
    • Remote support when you need it
    • 24/7 end to end online web shop
    • If we don’t have the equipment you are looking for – we will find it for you!

    Speak to our experts today