Fluke CNX3000 Wireless Multimeter

Work Faster, Safer and Easier with CNX Wireless Test Tools

Fluke's CNX Wireless Test Tools put tools, not your body, near live electrical panels. It's simple. Connect the remote modules, whether they are voltage modules, current clamps, flexible current loops or thermometers, and read the results on the CNX 3000 Wireless Multimeter from a safe distance. You can display the meter measurement, plus readings from up to 3 wireless modules.

Don't Get Bogged Down While Isolating Intermittent Electrical Faults

Timing is everything when trying to find an intermittent problem and the hard part is, it doesn't always show up when you have your meter connected. We've solved that problem with CNX – leave your CNX remote modules connected to log measurements and walk away to address other issues. You can then download the data for further analysis.

Work Safely Near Electrical Panels While Wearing Less PPE

Personal protective equipment (PPE) can save your life, but it's bulky, hot and hard to work in. With CNX, there's no need to work in front of live open panels or moving/hazardous machinery.

Picture having the ability to access live readings without being exposed to the live panel. It's easy. Just deenergize the cabinet, open the panel while wearing PPE and connect your CNX modules. Close the cabinet, reenergize and let the CNX multimeter work, reducing the risk of arc flash by separating yourself from hazardous measurement situations.

Testing 3-Phase is Now Faster and Cheaper

When your cabinet is deenergized, attach a CNX current clamp to each phase. Close, reenergize and start taking readings. What used to take hours and use costly equipment can be done in minutes with an affordable CNX wireless system.

Take 3-Phase Measurements in 1/3 the Time. Add your laptop and go from logging to analysis and diagnosis

You can solve problems faster by seeing live measurements from multiple test points on a single screen. With a CNX wireless test tool, you can:

Take 3-phase measurements in 1/3 the time

Add your laptop and go from logging to analysis and diagnosis

Record over time using the CNX wireless modules and monitor circuit load changes for an hour, a shift or a week

Use the CNX wireless USB adapter to collect logged data from remote modules by walking past a working module and downloading logged data

Perform for analysis with your PC and the CNX wireless test tool software. View data or graphs to see problems easily on the computer display

Features

  • The CNX 3000 Wireless Multimeter has all the essentials for convenient test and measurement troubleshooting.
  • AC and DC voltage measurements to 1000V
  • AC and DC current with 0.01 mA resolution
  • Continuity, resistance, diode test, capacitance and frequency measurements
  • MIN/MAX Recording
  • CAT III 1000 V, Cat IV 600 V; IP54
  • Plus, the CNX wireless enabled modules measure AC voltage, AC current and temperature, which display on the CNX Wireless Multimeter. Choose a standard clamp or flexible clamp to measure AC current. Mix and match modules to suit your unique measurement needs. Read the primary measurement on the main display, and up to three modules at any one time. Modules are available separately or as part of CNX kits.

 

Product Details

  • AC Voltage
  • Range ¹ / Resolution 600.0 mV / 0.1 mV
  • 000 V / 0.001 V
  • 00 V / 0.01 V
  • 0 V / 0.1 V
  • 1000 V / 1 V
  • Accuracy ², ³ 45 Hz to 500 Hz 1.0 % + 3
  • 500 Hz to 1 kHz 2.0 % + 3
  • ¹ All AC voltage ranges are specified from 1 % of range to 100 % of range.
  • ² Crest factor of ? 3 at full scale p to 500 V, decreasing linearly to crest factor < 1.5 at 1000 V.
  • ³ For non-sinusoidal waveforms, add –(2 % of reading + 2 % full scale) typical, for crest factor up to 3.
  • DC Voltage, Continuity, Resistance, Diode Test and Capacitance
  • Function
  • mV Range ¹ / Resolution 600.0 mV / 0.1 mV
  • Accuracy 0.09 % + 2
  • V Range ¹ / Resolution 6.000 V / 0.001 V
  • 00 V / 0.01 V
  • 0 V / 0.1 V
  • 1000 V / 1 V
  • Accuracy 0.09 % + 2
  • 15 % + 2
  • ))) Range ¹ / Resolution 600 ? / 1 ?
  • Accuracy Meter beeps at < 25 ?, beeper detects opens or shorts of 250 ?s or longer. ? Range ¹ / Resolution 600.0 ? / 0.1 ? 6.000 k? / 0.001 k? 60.00 k? / 0.01 k? 60.00 k? / 0.1 k? 600.0 k? / 0.001 M? 50.00 M? / 0.01 M? Accuracy 0.5 % + 2 0.5 % + 1 1.5 % + 3 Diode test Range ¹ / Resolution 2.000 V0.001 V Accuracy 1 % + 2 ?F Range ¹ / Resolution 1000 nF / 1 nF 10.00 ?F / 0.01 ?F 100.0 ?F / 0.1 ?F 9999 ?F ¹ / 1 ?F Accuracy 1.2 % + 2 10 % ¹ In the 9999 ?F range for measurements to 1000 ?F, the measurement accuracy is 1.2 % + 2. AC and DC Current Function mA AC (45 Hz to 1 kHz) Range ¹ / Resolution 60.00 mA / 0.01 mA 400.0 mA ³ / 0.1 mA Accuracy 1.5 % + 3 mA DC ² Range ¹ / Resolution 60.00 mA / 0.01 mA 400.0 mA / 0.1 mA Accuracy 0.5 % + 3 ¹ All AC current ranges are specified from 5 % of range to 100 % of range. ² Input burden voltage (typical): 400 mA input 2 mV/mA. ³ 400.0 mA accuracy specified up to 600 mA overload. Frequency Range ¹ / Resolution 99.99 Hz / 0.01 Hz 999.9 Hz / 0.1 Hz 9.999 kHz / 0.001 kHz 99.99 kHz / 0.01 kHz Accuracy 0.1 % + 1 ¹ Frequency is specified up to 99.99 kHz in volts and up to 10 kHz in amps. Input Characteristics Function OverloadProtection 1100 V RMS Input Impedance (nominal) > 10 M? < 100 pF Common Mode Rejection Ratio (1 k? unbalance) > 120 dB at DC, 50 Hz or 60 Hz
  • Normal Mode Rejection > 60 dB at 50 Hz or 60 Hz
  • OverloadProtection 1100 V RMS
  • Input Impedance
  • (nominal) > 10 M? < 100 pF Common Mode Rejection Ratio (1 k? unbalance) > 60 dB, DC to 60 Hz
  • OverloadProtection 1100 V RMS
  • Input Impedance
  • (nominal) > 10 M? < 100 pF Common Mode Rejection Ratio (1 k? unbalance) > 120 dB at DC, 50 Hz or 60 Hz
  • Normal Mode Rejection > 60 dB at 50 Hz or 60 Hz
  • Open circuit test voltage
  • OverloadProtection 1100 V RMS
  • Input Impedance
  • (nominal) < 2.7 V DC
  • Full scale To 6 M?: < 0.7 V DC
  • 50 M?: < 0.9 V DC
  • Typical short circuit current < 350 mA
  • OverloadProtection 1100 V RMS
  • Input Impedance
  • (nominal) < 2.7 V DC
  • Full scale To 6 M?: 2.000 V DC
  • Typical short circuit current < 1.1 mA mA Overload Protection Fused, 44/100 A, 1000 V FAST Fuse Overload 600 mA overload for 2 minutes maximum, 10 minutes rest minimum MIN/MAX Recording DC functions The specified accuracy of the measurement function ± 12 counts for changes > 350 mS in duration
  • AC functions The specified accuracy of the measurement function ± 40 counts for changes > 900 mS in duration
  • General Specifications
  • Maximum voltage between any terminal and earth ground 1000 V DC or AC RMS
  • ? fuse protection from A inputs 0.44 A (44/100 A, 440 mA), 1000 V FAST Fuse, Fluke specified part only
  • Display (LCD) Update rate: 4/sec
  • Volts, amps, ohms: 6000 counts
  • Frequency: 10,000 counts
  • Capacitance: 1,000 counts
  • Battery type Three AA Alkaline batteries, NEDA 15A IEC LR6
  • Battery life 300 hours minimum
  • Temperature Operating: -10 °C to 50 °C Storage: -40 °C to 60 °C
  • Relative humidity 0 % to 90 % (0 °C to 35 °C)
  • 0 % to 75 % (35 °C to 40 °C)
  • 0 % to 45 % (40 °C to 50 °C)
  • Altitude Operating: 2,000 m
  • Storage: 12,000 m
  • Temperature coefficient 0.1 X (specified accuracy) / °C (< 18 °C or > 28 °C)
  • Wireless frequency 2.4 GHz ISM Band 20 meter range
  • Size (H x W x L) 4.75 cm x 9.3 cm x 20.7 cm (1.87 in x 3.68 in x 8.14 in)
  • Weight 340 g (12 oz)
  • Safety standards US ANSI: ANSI/ISA 61010-1 / (82.02.01): 3rd edition
  • CSA: CAN/CSA-C22.2 No 61010-1-12: 3rd edition
  • CE European: IEC/EN 61010-1:2010
  • Electromagnetic compatibility
  • EMI, RFI, EMC, RF EN 61326-1:2006, EN 61326-2-2:2006
  • ETSI EN 300 328 V1.7.1:2006, ETSI EN 300 489
  • 8.1:2008, FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249
  • FCCID : T68-FWCS IC:6627A-FWCS
  • Ingress Protection (IP) rating IP54

 

    Downloads

    Committing to 3, 6 or 12 Months?

    Call us for fantastic long term hire rates.

    Contact Us

    NEED TECHNICAL SUPPORT?

    Call us for fantastic long term hire rates.

    Tech Support

    The Powertech Difference

    • Huge inventory of test and measurement equipment
    • Calibration labs for Electrical, Pressure, Torque, Temperature, Flow, Dimensional and PPE
    • Remote support when you need it
    • 24/7 end to end online web shop
    • If we don’t have the equipment you are looking for – we will find it for you!

    Speak to our experts today